Products search search close

IO752: PROFINET Device I/O Module

Configurable PROFINET Device I/O module, with Simulink driver blocks

The IO752 I/O module is a PROFINET module to connect real-time target machines to external devices.

The IO752 handles the complete data exchange between the connected PROFINET Controller and the real-time application. The data exchange is processed via a dual-port memory. The module acts as one PROFINET Device exclusively. 

This I/O module is ideal for rapid control prototyping of devices in industrial automation plants such as motor controllers, sensors, I/O stations, and robots. Furthermmore, the IO752 can be used to perform hardware-in-the-loop (HIL) simulations for PLC testing, virtual commissioning, and factory acceptance tests using MATLAB® and Simulink®.

The IO752 I/O module is fully compatible with the Simulink Real-Time™ workflow. The extensive Simulink Real-Time driver blockset offers comprehensive functionality, and firmware updates are easily available, as the Setup driver block downloads microcontroller firmware each time a target application is initialized.

Key Features

  • 2x 10BASE-T/100BASE-TX isolated, auto-crossover function Ethernet connectors enable easy network integration
  • Compatible with Real-Time Cyclic Protocol (RTC) – Class 1 & Class 2 (unsynchronized), Class 3 (synchronized)
  • Isochronous real-time allows fast and synchronous communication at 250 µs
  • Simulates all PROFINET Devices from all vendors 
  • Seamless import of AML files from TIA Portal to easily set up multiple device simulation 
  • Acyclic communication
  • DMA enables fast data exchange on PCI bus 
 
Physical  
Form factor PCI/PCIe/mPCIe 
Power requirements 650 mA @ +3.3 V DC
Bus 32 bit/33 MHz, Revision 3 of PMC specification, P1386.1 
Connectors 2x RJ45 socket
Environmental  
Operating temperature 0 °C to +70 °C (PCI, mPCIe) 
0 °C to +55 °C (PCIe)* 
Certification  CE
I/O Access
 
Maximum number of input bytes  1024 
Maximum number of output bytes  1024 
Maximum number of sub-modules  128 (default**) 
Minimum cycle time RT  1 ms 
Minimum cycle time IRT  250 µs 
Total maximum number of application relations (AR)  128 (64 for IRT communication) 
Acyclic communication  Read/Write records 
Maximum number of user-defined records  4096 
Maximum number of record payload bytes  1024 
Maximum number of application relations (AR)  1 (default**) 
Custom I&M information  On demand 
Sending user-defined alarms  On demand 
Baud rate  100 MBit/s
Data transport layer  Ethernet II, IEEE 802.3 
* Special hardware version is available which supports operating temperatures from 0 °C to +70 °C
** Custom firmware is available supporting more sub-modules and application relations
Item ID Product Name Components
2X752* IO752
  • 1 x IO752 I/O module
  • Driver block library for Simulink Real-Time™
  • Comprehensive documentation and Simulink example models 
  • Installation into real-time target machine

Key to X in Item ID
Please replace the X with the code number of the specific target machine into which this I/O module shall be installed:

  • A = Performance real-time target machine (PCI)
  • B = Performance real-time target machine (PCIe)
  • C = Mobile, Baseline and Unit real-time target machines (mPCIe)

Pricing information
We don't publish pricing information on our website. Upon request by e-mail or phone we can provide a complete price list covering our entire product portfolio in various currencies. We recommend that you get in touch with us to discuss your specific needs. We can then quickly provide you with a tailored quotation including technical and pricing information.

 

IO752: PROFINET Controller I/O module 

Included in the Delivery

Common Applications

Supported target machines

Resources

Follow Speedgoat LinkedIn